Duct Leakage Test in Harrison township (Gloucester), NJ

Maintain top HVAC efficiency and stay aligned with local energy codes using trusted duct leakage test in Harrison township (Gloucester), NJ. Our certified technicians inspect and measure air leakage in ductwork, enabling homeowners and builders to boost comfort, prevent energy waste, and adhere to state guidelines.

Why Duct Leakage Test is Important In Harrison township (Gloucester), NJ

States and municipalities have adopted the 2015 IECC, International Energy Conservation Code for single-family buildings and the 2018 International Energy Conservation Code for multi-family buildings. The change will bring notable implications for home builders and HVAC contractors working throughout the state. A Duct Leakage Test together with a Blower Door Test must now be performed in all newly built or remodeled homes to comply with the 2015 regulations. Did you know that ducts are one of the primary sources of air leakage in homes throughout Pennsylvania, New Jersey, and Delaware? Leaked air can increase monthly energy costs, stress your HVAC system, and scatter dust and insulation across your living areas. This makes duct leakage test an important requirement for homes regardless of age. Keep reading to understand why duct leakage test is necessary and how it can help you.

What Our Clients Say

How a Duct Leakage Test Is Conducted

To perform a duct leakage test in Harrison township (Gloucester), NJ, the technician begins by sealing every supply and return register except for the primary return or air handler unit. A duct blaster, designed as a calibrated testing fan, is then attached to the duct system. Its purpose is to depressurize the ducts and uncover leak points.

The duct blaster works in sync with a precision pressure sensor to assess airflow and find duct leaks without disturbing your living space. A duct leakage test — often referred to as a duct blaster test — identifies air loss in your ducts, allowing you to find the most effective ways to seal them.

duct leakage test is quick, neat, and intentionally non-intrusive for anyone living in the home. Most tests in Harrison township (Gloucester), NJ are completed within 30 to 60 minutes, and the improvements can benefit your home’s comfort and efficiency for years.

How to Measure Duct Leakage

Duct leakage is measured in cubic feet per minute (CFM) per 100 square feet of conditioned space. Your technician uses a nanometer to read small pressure variations, helping determine the volume of air escaping through the ducts. Understanding this number allows you to pinpoint problem areas, assess needed improvements, and confirm whether your home satisfies local energy code requirements in Harrison township (Gloucester), NJ.

Cost of Excessive Duct Leakage

If you are experiencing high utility bills, uneven temperatures, or frequent HVAC repairs, duct leakage may be the cause. According to ENERGY STAR, duct leakage causes homeowners to lose 20%–30% of their conditioned air on average. Hot or cold outside air creeping into your system forces the HVAC to work inefficiently, increasing energy spending and reducing comfort.

Overworked equipment also brings more system failures and higher repair expenses. Proper duct sealing helps strengthen the long-term function of your HVAC system, improving its lifespan and reducing ongoing maintenance costs.

Duct leaks can also allow dust, mold spores, excess moisture, and other contaminants into the duct system. This can irritate allergies, harm the air quality inside, and cause expensive hidden structural damage as time goes on.

How to Properly Seal Ductwork in an Old Home

The 2015 IRC/IECC mandates fully sealed duct systems in new homes, made from energy-efficient materials like mastic, foil tape, and proper insulation. But what happens when leaks are trapped deep inside wall or ceiling cavities?

Aerosol sealing technology (AeroSeal) helps target hard-to-reach openings deep within ducts. To start this method, all vents are blocked except for one access location. The HVAC system is isolated, and a machine is attached to the ducts. It pressurizes the ducts and applies a fine aerosol sealant that fills tiny openings where standard sealing cannot reach.

This method is ideal for small to medium leaks. However, any large openings will still need manual sealing with mastic and tape. Technicians conduct duct leakage test before and after aerosol sealing to see how much the leakage dropped and ensure the treatment worked properly.

Common Areas of Duct Leakage

The most common area where ducts leak air is around the joints. Ductwork uses several metal parts pressed together with tight fittings and metal bands, though these points are rarely airtight.

As your HVAC system runs through seasonal heating and cooling, the ducts experience ongoing expansion and contraction. Over time, this movement causes the joints to loosen, creating gaps and leaks — which is why a duct leakage test is recommended for both new and older homes in Harrison township (Gloucester), NJ.

Many energy auditors check for leaks by feeling along the ductwork and using a small tool to gauge the size of gaps between joints. If your duct system hasn’t been sealed with mastic and approved tape, there is a strong likelihood that leakage is happening.

What Is an Acceptable Amount of Duct Leakage per Energy Code?

To achieve a passing duct leakage result, your system should measure under 4 CFM per 100 square feet with the air handler installed, or 3 CFM per 100 square feet without the air handler installed. For new construction, passing a duct leakage test is required before a home can receive an occupancy certificate.

If your home in Harrison township (Gloucester), NJ does not pass a duct leakage test, you are likely paying more than necessary for heating and cooling — and placing long-term strain on your HVAC equipment. Meeting the 3–4 CFM requirement is fundamental not only for code adherence but for boosting your home’s long-term efficiency and comfort.

Your technician will also share expert solutions for tackling leakage problems so you can pass the test, cut down utility expenses, and improve overall comfort and efficiency.

Local Energy Audits — affordable duct leakage test in Harrison township (Gloucester), NJ

Local Energy Audits proudly serves customers throughout Harrison township (Gloucester), NJ and surrounding areas. We specialize in identifying duct leakage and energy inefficiencies using blower door tests and duct leakage tests. Whether you’re building a new home or improving an existing one, we’re here to help.
If you’d like to schedule a test, call us during business hours or contact us online to request an appointment.

The Duct Leakage Test Steps Explained

A duct leakage test begins by applying duct mask tape to seal every duct and register on both the supply and return sides.

After the registers are sealed, we attach the duct tester to either the unit itself or a main return.

The ducts are then reduced to a depressurized state of 25 Pascals. With them depressurized, the nanometer gives us the duct leakage reading.

Schedule Your Duct Leakage Test in Harrison township (Gloucester), NJ

Ensure your HVAC system stays efficient, compliant, and operating at peak performance with expert duct leakage test in Harrison township (Gloucester), NJ. Whether you’re a homeowner improving home comfort or a contractor finishing required inspections, our certified team delivers fast, accurate, and affordable testing.

We use industry-standard duct blaster equipment and offer direct on-site guidance to help you pass your test, lower energy waste, and protect your HVAC system’s long-term health.

Serving homeowners, builders, and contractors across Harrison township (Gloucester), NJ with dependable and energy-efficient testing solutions.